400 Technical data
ACH550-01 User's Manual
Input power (mains) cable
The following table gives copper and aluminium cable types for
different load currents. These recommendations apply only for
the conditions listed at the top of the table.
Dimension the cables according to local safety regulations,
appropriate input voltage and the load current of the drive. In
any case, the cable must be less than the maximum limit defined
by the terminal size (see section Input power and motor
connection terminals on page 402).
IEC NEC
Based on:
EN 60204-1 and IEC 60364-5-2/2001
PVC insulation
30 °C (86 °F) ambient temperature
70 °C (158 °F) surface temperature
cables with concentric copper shield
not more than nine cables laid on cable
ladder side by side.
Based on:
NEC Table 310-16 for copper
wires
90 °C (194 °F) wire insulation
40 °C (104 °F) ambient
temperature
not more than three current-
carrying conductors in
raceway or cable, or earth
(directly buried)
copper cables with
concentric copper shield.
Max
load
current
A
Cu
cable
mm
2
Max
load
current
A
Al cable
mm
2
Max load
current
A
Cu wire size
AWG/kcmil
14 3x1.5 61 3x25 22.8 14
20 3x2.5 75 3x35 27.3 12
27 3x4 91 3x50 36.4 10
34 3x6 117 3x70 50.1 8
47 3x10 143 3x95 68.3 6
62 3x16 165 3x120 86.5 4
79 3x25 191 3x150 100 3
98 3x35 218 3x185 118 2
119 3x50 257 3x240 137 1
153 3x70 274 3x
(3x50)
155 1/0
Zobrazit stránku 403