258 Parameter listing and descriptions
ACH550-01 User's Manual
5 = THERM(0) – Sensor configuration uses a thermistor.
• Motor thermal protection is activated through a digital input. Connect
either a normally closed thermistor relay or a PTC sensor to a digital
input.
• When the digital input is ‘0’, the motor is overheated.
• See the connection figures on page 256.
• The table below and the graph on page 257 show the resistance
requirements for a PTC sensor connected between 24 V and digital
input as a function of the motor operating temperature.
6 =
THERM(1) – Sensor configuration uses a thermistor.
• Motor thermal protection is activated through a digital input. Connect
a normally open thermistor relay to a digital input.
• When the digital input is ‘1’, the motor is overheated.
• See the connection figures on page 256.
3502 INPUT SELECTION 1…8
Defines the input used for the temperature sensor.
1 =
AI1 – PT100 and PTC
2 =
AI2 – PT100 and PTC
3…8 =
DI1…DI6 – Thermistor and PTC.
3503 ALARM LIMIT -10…200 °C
Defines the alarm limit for 0…5000 ohm
the motor temperature measurement. 0…1
• At motor temperatures above this limit, the drive displays an alarm
(2010,
MOTOR TEMP)
For thermistors or PTC connected to digital input:
0 – De-activated.
1 – Activated.
3504 FAULT LIMIT -10…200 °C
Defines the fault limit for 0…5000 ohm
the motor temperature measurement. 0…1
• At motor temperatures above this limit, the drive displays a fault (9,
MOT OVERTEMP) and stops the drive.
For thermistors or PTC connected to digital input:
0 – De-activated.
1 – Activated.
Code Description Range
Temperature Resistance
Normal < 3 kohm
Excessive > 28 kohm