244 Parameter listing and descriptions
ACH550-01 User's Manual
3023 WIRING FAULT 0=DISABLE, 1=ENABLE
Defines the drive response to cross wiring faults and to earth faults
detected when the drive is NOT running. When the drive is not running,
it monitors for:
Improper connections of input power to the drive output (the drive can
display fault 35,
OUTP WIRING if improper connections are detected).
Earth faults (the drive can display fault 16,
EARTH FAULT if an earth
fault is detected). Also, see parameter 3017
EARTH FAULT.
Note: Disabling wiring fault (earth fault) may void the warranty.
0 =
DISABLE – No response to either of the above monitoring results.
1 =
ENABLE – Displays a fault when this monitoring detects problems.
3024 CB TEMP FAULT 0=DISABLE, 1=ENABLE
Defines the drive response to control board overheating. Not for drives
with an OMIO control board.
0 =
DISABLE – No response
1 =
ENABLE – Displays a fault (37, CB OVERTEMP) and the drive coasts to
stop.
Code Description Range