224 Parameter listing and descriptions
ACH550-01 User's Manual
2209 RAMP INPUT 0 -6…7
Defines control for forcing the speed to 0 with the currently used
deceleration ramp (see parameters 2203
DECELER TIME 1 and 2206
DECELER TIME 2).
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the speed
to 0.
• Activating the digital input forces the speed to 0, after which the
speed will stay at 0.
• De-activating the digital input: speed control resumes normal
operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing
the speed to 0.
•See
DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for
forcing the speed to 0.
The command word is supplied through fieldbus communication.
The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines inverted digital input DI1 as the control for forcing
the speed to 0.
• De-activating the digital input forces the speed to 0.
• Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for forcing the speed to 0.
•See
DI1(INV) above.
Code Description Range