226 Parameter listing and descriptions
ACH550-01 User's Manual
2302 INTEGRATION TIME 0…600.00 s
Sets the integration time for the speed controller.
• The integration time defines the rate at which the controller output
changes for a constant error value.
• Shorter integration times correct continuous errors faster.
• Control becomes unstable if the integration time is too short.
• The figure shows the speed controller output after an error step (error
remains constant).
Note: You can use parameter 2305
AUTOTUNE RUN to automatically set
the integration time.
Code Description Range
T
I
Controller output
%
K
p
· e
K
p
· e
e = Error value
K
p
= Gain = 1
T
I
= Integration time > 0
T
D
= Derivation time = 0
t