304 Parameter listing and descriptions
ACH550-01 User's Manual
8117 NR OF AUX MOT 0…4
Sets the number of auxiliary motors.
Each auxiliary motor requires a relay output, which the drive uses to
send start/stop signals.
The Autochange function, if used, requires an additional relay output
for the speed regulated motor.
The following describes the set-up of the required relay outputs.
Relay outputs
As noted above, each auxiliary motor requires a relay output, which the
drive uses to send start/stop signals. The following describes how the
drive keeps track of motors and relays.
The ACH550 provides relay outputs RO1…RO3.
An external digital output module can be added to provide relay
outputs RO4…RO6.
Parameters 1401…1403 and 1410…1412 define, respectively, how
relays RO1…RO6 are used – the parameter value 31 (PFA) defines
the relay as used for PFA.
The ACH550 assigns auxiliary motors to relays in ascending order. If
the Autochange function is disabled, the first auxiliary motor is the
one connected to the first relay with a parameter setting = 31 (PFA),
and so on. If the Autochange function is used, the assignments rotate.
Initially, the speed regulated motor is the one connected to the first
relay with the parameter setting = 31 (PFA), the first auxiliary motor is
the one connected to the second relay with a parameter setting =
31 (PFA), and so on.
The fourth auxiliary motor uses the same reference step, low
frequency and start frequency values as the third auxiliary motor.
Code Description Range
ACH550
Standard PFA mode
Zobrazit stránku 307