280 Parameter listing and descriptions
ACH550-01 User's Manual
4021 ACT2 MAXIMUM -1000…1000%
Sets the maximum value for
ACT2.
See 4018
ACT1 MINIMUM.
4022 SLEEP SELECTION -6…7
Defines the control for the PID sleep function.
0 =
NOT SEL– Disables the PID sleep control function.
1 =
DI1 – Defines digital input DI1 as the control for the PID sleep
function.
• Activating the digital input activates the sleep function.
• De-activating the digital input restores PID control.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for the
PID sleep function.
•See
DI1 above.
7 =
INTERNAL – Defines the output rpm/frequency, process reference,
and process actual value as the control for the PID sleep function.
• Refer to parameters 4025
WAKE-UP DEV and 4023 PID SLEEP LEVEL.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for the
PID sleep function.
• De-activating the digital input activates the sleep function.
• Activating the digital input restores PID control.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for the PID sleep function.
•See
DI1(INV) above.
Code Description Range