260 ACS550-01/U1 User’s Manual
Diagnostics
Flashing red LED
To reset the drive for faults indicated by a flashing red LED:
Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
Press RESET from the control panel.
Turn the power off for 5 minutes.
Depending on the value of 1604
FAULT RESET SEL, the following could also be used to
reset the drive:
digital input
serial communication.
When the fault has been corrected, the motor can be started.
History
For reference, the last three fault codes are stored into parameters 0401, 0412,
0413. For the most recent fault (identified by parameter 0401), the drive stores
additional data (in parameters 0402…0411) to aid in troubleshooting a problem. For
example, parameter 0404 stores the motor speed at the time of the fault.
The Assistant Control Panel provides additional information about the fault history.
See section Fault Logger mode on page 57 for more information.
To clear the fault history (all of the Group 04: FAULT HISTORY parameters):
1. Using the control panel in the Parameters mode, select parameter 0401.
2. Press EDIT (or ENTER on the Basic Control Panel).
3. Press UP and DOWN at the same time.
4. Press SAVE.
Correcting alarms
The recommended corrective action for alarms is:
Determine if the alarm requires any corrective action (action is not always
required).
Use the table in section Alarm listing below to find and address the root cause of
the problem.