©ABB Ltd -15
Jumpers and Switches
The E-Clipse Bypass ships with DCOM / GND Jumper &
START EN 1 Jumper installed at the factory
Therefore, the E-Clipse Bypass will run out of the box!
If your customer has normally closed (N.C.) safety
input(s), remove the jumper from DI3 (Pin X2:7) and
insert customer safety contact.
If customer has more than one safety input and / or
Damper End-switch either use another bypass Macro or
individually program DIs in Group 16