20 ABB industrial drives ACS880 single drives | Catalog
du/dt filters
du/dt filtering suppresses inverter output voltage spikes
and rapid voltage changes that stress motor insulation.
Additionally, du/dt filtering reduces capacitive leakage
currents and high frequency emission of the motor cable as
well as high frequency losses and bearing currents in the
motor. The need for du/dt filtering depends on the motor
insulation. For information on the construction of the motor
insulation, consult the manufacturer.
If the motor does not fulfil the following requirements, the
lifetime of the motor might decrease. Insulated N-end
(nondriven end) bearings and / or common mode filters are
also required for motor bearing currents with motors bigger
than 100 kW. For more information please see the ACS880
hardware manuals.
How to select a filter according to the motor. Please see
below:
NOCH0016-60NOCH0016-62 NOCH0016-65 FOCH0610-70
Filter selection table for ACS880
Motor type Nominal AC supply voltage Requirements for
Motor insulation system
ABB du/dt and common mode filters,
insulated N-end motor bearings
P
N
< 100 kW and
frame size < IEC 315
100 kW P
N
< 350 kW or
IEC 315 frame size <
IEC 400
P
N
< 134 hp and
frame size < NEMA 500
134 hp P
N
< 469 hp or
NEMA 500 frame
size NEMA 580
ABB motors
Random-wound
M2__, M3__ and M4__
U
N
≤ 500 V
Standard
-
+ N
500 V < U
N
≤ 600 V
Standard + du/dt + du/dt + N
or
Reinforced
-
+ N
600 V < U
N
≤ 690 V
(cable length ≤ 150 m)
Reinforced + du/dt + du/dt + N
600 V < U
N
≤ 690 V
(cable length > 150 m)
Reinforced
-
+ N
Form-wound
HX__ and AM__
380 V < U
N
≤ 690 V
Standard n.a. + N + CMF
Old* form-wound
HX__ and modular
380 V < U
N
≤ 690 V
Check with the motor
manufacturer
+ du/dt with voltages over 500 V + N + CMF
Random-wound
HX__ and AM__**
0 V < U
N
≤ 500 V
Enmelled wire with
fiber glass taping
+ N + CMF
500 V < U
N
≤ 690 V
+ du/dt + N + CMF
HDP Consult the motor manufacturer.
* manufactured before 1.1.1998
** For motors manufactured before 1.1.1998, check for additional instructions with the motor manufacturer.