I-E67-TB82FF-2A February 13, 2002
36
ANALOG INPUT 2 - FUNCTION BLOCK (cont’d)
IDX Name Description Bytes ST AR Default Valid Range Note
21 BLOCK_ALM Unacknowledged 1 D R/W 0
Alarm State 1 D R 0
Time Stamp 8 D R 0
Sub-code 2 D R 0
Value 1 D R 0
22 ALARM_SUM Current 2 D R 0
Unacknowledged 2 D R 0
Unreported 2 D R 0
Disabled 2 S R/W 0
23 ACK_OPTION
Automatic
Acknowledge Option
2SR/W 0
0 – Disable
1 – Enable
24 ALARM_HYS Alarm Hysteresis 4 S R/W 0.5% 0 to 50 %
25 HI_HI_PRI High-High Priority 1 S R/W 0 0 to 15
26 HI_HI_LIM High-High Limit 4 S R/W 300 °C Note M
27 HI_PRI High Priority 1 S R/W 0 0 to 15
28 HI_LIM High Limit 4 S R/W 300 °C Note M
29 LO_PRI Low Priority 1 S R/W 0 0 to 15
30 LO_LIM Low Limit 4 S R/W -20 °C Note M
31 LO_LO_PRI Low-Low Priority 1 S R/W 0 0 to 15
32 LO_LO_LIM Low-Low Limit 4 S R/W -20 °C Note M
33 HI_HI_ALM Unacknowledged 1 D R/W 0
Alarm State 1 D R 0
Time Stamp 8 D R 0
Sub-code 2 D R 0
Value 4 D R 0
34 HI_ALM Unacknowledged 1 D R/W 0
Alarm State 1 D R 0
Time Stamp 8 D R 0
Sub-code 2 D R 0
Value 4 D R 0
35 LO_ALM Unacknowledged 1 D R/W 0
Alarm State 1 D R 0
Time Stamp 8 D R 0
Sub-code 2 D R 0
Value 4 D R 0
36 LO_LO_ALM Unacknowledged 1 D R/W 0
Alarm State 1 D R 0
Time Stamp 8 D R 0
Sub-code 2 D R 0
Value 4 D R 0